Adjusting the TV-MPCXP driver properties
TruVu™ MPC Processor
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
37
Calendars
Calendars are provided in the driver for BACnet compatibility only. Instead, use the
Schedules
feature in the i-Vu®
interface.
Common and Specific Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Common alarms:
Specific alarm:
•
All Programs Stopped
•
Excessive COV
•
Program Stopped
•
Locked I/O
•
Controller Halted
•
Control Program
•
Duplicate Address
•
Dead Controller Timeout
NOTE
To set up alarm actions for controller generated alarms, see
Setting up alarm actions
in the i-Vu® Help.
Controller Generated Alarm
Description
Short message shown on the
Alarms
page or in an alarm action when this type of
alarm is generated.
Events
Alarm Category and Alarm
Template
See
Setting up an alarm source in the i-Vu® interface
in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from the TV-MPCXP.
Notification Class
In a typical i-Vu® system, the Notification Class is 1; however, if needed, you can
associate a different notification class with the alarm. See
Notification Classes
(page 36) to set up alarm delivery options for a specific Notification Class.
Custom Translation Tables
Applies to the analog input of an attached expander.
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to provide on the output wire of the Analog Input microblock. In the navigation
tree, select
Custom Translation Table #1
,
#2
, or
#3
. The
Properties
page has instructions.
For the input to use the translation table, go to the control program's
Properties
page >
I/O Points
tab. Click the
analog input in the
Name
column. On the
Details
tab, set
Sensor Type (Scaling Method)
to
Non-Linear, Custom
Table #__
.