All data will be lost when set to
ON position.
Number Of Channel Modules:
1
1 to 3
1 to 4
1 to 4
1
2
3-4
5-6
7-8
ON = NVRAM Erased & Reset
OFF = NVRAM Maintained
ON = Master Channel outputs Master
Channel flow rate on secondary
analog output.
OFF = Master Channel outputs GUN flow
rate on secondary analog output.
RIO Baud rate position
3
4
Baud Rate
OFF OFF = 57.6 KB
OFF ON
= 115.2 KB
ON
OFF = 230.4 KB
ON
ON
= 230.4 KB
SIO Baud rate position
5
6
Baud Rate
OFF OFF = 19.2 KB
OFF ON
= 4.8 KB
ON
OFF = 9.6 KB
ON
ON
= 38.4 KB
RIO Rack Size position
7
8
Size
OFF OFF = 1/4 Rack
OFF ON
= 1/2 Rack
ON
OFF = 3/4 Rack
ON
ON
= Full Rack
OFF
OFF
OFF
OFF
OFF
* Inserting this jumper adds a 120 Ohm termination resistor across the RS-485 RX+ and RX- lines.
** Inserting this jumper adds a 120 Ohm termination resistor across the Ransburg CAN Bus.
Position
Description
Comments
Default Setting
INTERFACE MODULE DIP SW2 SETTINGS
LN-9400-00-R11 (08/2018)
76 / 96
www.carlisleft.com
MAINTENANCE