CDE360 Vector Control AC Drive Chapter 6 Parameters Description
E6.00
①
Range: 0~4
Default: 0
Multi-pump
control mode
This series AC drive support multi-pump control modes.
Each of them is apply to different application area with different configuration and
operation logic:
0:Inactive
The AC drive can only work at single pump control mode.
1:Frequency pump fixed,No auto change
The AC drive controls a specific adjustable speed motor,other auxiliary motors
are all controlled via relays.
This mode needs to configurate the system as shown in the top figure of next
page.
The auxiliary motor will be directly connected to power grid when adding a
pump.
2:Frequency pump fixed,Support auto change
Base on mode 1,auxiliary motors can be auto changed.
3:Frequency pump circulation,No auto change
Any pump can be connected to power grid or directly controlled by AC drive in
this mode.
This mode needs to configurate the system as shown in the bottom figure of
next page.
The auxiliary motor will be softly start by AC drive when adding a pump.
4:Frequency pump circulation,Support auto change
Base on mode 3,all motors can be auto changed.
Table 6- 15 multi-pump control mode
Multi-pump
control mode
Frequency
pump
Auto
change
Configuration
1
Fixed
Nonsupport
The top figure
of next page.
2
Fixed
Support
3
Unfixed
Nonsupport
The bottom
figure of next
page.
4
Unfixed
Support