CDE360 Vector Control AC Drive Chapter 6 Parameters Description
E5.12
Range: 0.0~999.9
Default: 50.0
PID proportional
gain Kp2
Unit: %
Same with
E5.09
(PID proportional gain Kp1).
E5.13
Range: 0.01~99.99
Default: 2.00
PID integral time
Ti2
Unit: Sec
Same with
E5.10
(PID integral time Ti1).
E5.14
Range: 0.000~9.999
Default: 0.000
PID differential
time Td2
Unit: Sec
Same with
E5.11
(PID differential time Td1).
In some applications, PID parameters switchover is required when one group of PID parameters
cannot satisfy the requirement of the whole running process.
The PID regulator has two groups of proportional gain,integral time and differential time.
E5.09
~
E5.11
is the first group parameters,and
E5.12
~
E5.14
is the second.
The switchover can be implemented via
E5.15
(PID parameter switchover condition).
E5.15
Range: 0~2
Default: 0
PID parameter
switchover
condition
Used for PID two groups parameters selection.
0:No switchover
Always use the first group parameters(
E5.09
~
E5.11
).
1:Switchover via X terminals
Use the first group parameters(
E5.09
~
E5.11
) when the X terminal is
allocated with function No.40(PID parameter switchover) is valid,and the
second(
E5.12
~
E5.14
) when X terminal is invalid.
2:Automatic switchover based on deviation
Automatic switchover according to
E5.16
(PID parameter switchover
deviation 1)and
E5.17
(PID parameter switchover deviation 2).
Use the first group parameters(
E5.09
~
E5.11
) when the absolute
value of the deviation between PID feedback and PID setting is smaller
than than the value of
E5.16
,and the second when higher than
E5.17
.
If the absolute value of deviation is between
E5.16
and
E5.17
,PID
regulator will use the linear interpolated value of two groups of parameters
values,see the description of the following Figure.
E5.16
Range:
E5.03
~
E5.17
Default: 20.0
PID parameter
switchover
deviation 1
Unit: %
The unit and resolution will be changed according to
E5.00
and
E5.01
.
See the following figure.