CDE360 Vector Control AC Drive Chapter 6 Parameters Description
E5.02
Range:
E5.03
~6553.5
Default: 100.0
Maximum setting
of PID
engineering unit
Unit: %
The unit and resolution will be changed according to
E5.00
and
E5.01
.
E5.02
corresponds to 0% in AC drive,and affects the following
parameters:
A0.20
(PID reference)
A0.21
(PID feedback)
E5.03
Range: 0.0~
E5.02
Default: 0.0
Minimum setting
of PID
engineering unit
Unit: %
The unit and resolution will be changed according to
E5.00
and
E5.01
.
E5.03
corresponds to 0% in AC drive,and affects the following
parameters:
A0.20
(PID reference)
A0.21
(PID feedback)
E5.04
Range: 0~6
Default: 0
PID setting
source
0:
E5.05
+UP/DOWN
1: AI1
2: AI2
3: AI3
4: X6/FI
5: Multi-Reference
6: Communication
E5.05
Range:
E5.03
~
E5.02
Default: 50.0
PID digital setting
Unit: %
This parameter is used for PID setting value when
E5.04
= 0.
The unit and resolution will be changed according to
E5.00
and
E5.01
.
E5.04
is used to select the channel of target process PID setting. The PID setting and
feedback’s unit will be changed based on engineering unit.And their value will be converted into
relative value based on
E5.03
and
E5.02
.
The purpose of PID control is to make the PID setting and PID feedback equal.
E5.06
Range: 0.00~99.99
Default: 0.00
PID setting
change time
Unit: Sec
The time for PID setting value changing from
E5.03
to
E5.02
.
E5.07
Range: 0~8
Default: 0
PID feedback
source
This parameter is used for setting PID feedback source.
0: AI1
1: AI2
2: AI3
3: AI1-AI2
4: X6/FI
5: AI1+AI2
6: MAX(|AI1|, |AI2|)
7: MIN(|AI1|, |AI2|)
8: Communication
E5.08
Range: 0.00~60.00
Default: 0.00
PID feedback
filter time
Unit: Sec
This parameter determines the AC drive response speed of PID feedback.