CDE360 Vector Control AC Drive Chapter 6 Parameters Description
-
104
-
b1.19
Range: 0.0~3000.0
Default: 0.0
Forward/Reverse
rotation
dead-zone time
Unit: s
It is used to set the time when the output is 0Hz at transition of the drive
forward rotation and reverse rotation, as shown in the following figure.
输出频率
Hz
时间
t
死区时间
正转
反转
Figure 6- 7 Forward/reverse rotation dead-zone time
b1.20
Range: 0~1
Default: 0
Reverse control
0: Enabled
1: Disabled
It is used to set whether the drive allows reverse rotation. In the
applications where reverse rotation is prohibited, set this parameter to 1.
b1.21
Range: 0~1
Default: 1
Stop key function
STOP/RST key stop effective selection of functional mode.
0: STOP/RST key enabled only in keypad control
1: STOP/RST key enabled in any operation mode
Because the key of STOP/RST is multiplexed, when the key is used to
reset fault, it is enabled always.
b1.22
Range: 0~1
Default: 1
Startup
protection
0: No 1: Yes
This parameter is used to set whether to enable the safety protection. If it
is set to 1, the drive does not respond to the run command valid upon
drive power-on (for example, an input terminal is ON before power-on).
The drive responds only after the run command is canceled and becomes
valid again.
In addition, the drive does not respond to the run command valid upon
fault reset of the drive. The run protection can be disabled only after the
run command is canceled.
In this way, the motor can be protected from responding to run commands
upon power-on or fault reset in unexpected conditions.