CDE360 Vector Control AC Drive Chapter 6 Parameters Description
F0.24
Range: 0~4
Default: 0
Frequency
selection for
continuing to run
upon fault
If a fault occurs during the running of the AC drive and the handling of
fault is set to "Continue to run", the AC drive displays “AL”+fault code and
continues to run with the frequency set in
F0.24
.
0: Current running frequency
1: Setting frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality(F0.25)
F0.25
Range: 0.0~100.0
Default: 100.0
Backup
frequency upon
abnormality
Unit: %
The setting of
F0.25
is a percentage relative to the maximum frequency
(
b0.00
).
F0.26
Range: 0~1
Default: 0
Fire mode enable
0: Disable 1: Enable
If the fire mode is enabled, the X terminal set the function 58 and the X
terminal is valid, then drive enter fire mode control. If the frequency source
is PID then system increases a value of
F0.28
to PID setting, otherwise
drive run with the frequency of
F0.27
.
If drive is in fire mode control, system displays fire mode alarm code and
any other fault or alarm code will not be displayed. If the fault source is
from hardware(for example: overvoltage, overcurrent and so on) then
drive will be stop, once these hardware faults disappeared drive will
resume to fire mode control and run with the frequency of
F0.27
.
In fire mode the start and stop command is valid.
If drive receive a fire mode signal in stop status then drive will not run
automatically..
F0.27
Range: 0.00~
b0.00
Default: 50.00
Fire mode
frequency
Unit: Hz
It is used to set the aim frequency when drive is in fire mode control. More
details please see the description of parameter
F0.26
.
F0.28
Range: 0.0~200.0
Default: 10.0
Fire mode PID
setting increase
Unit: %
It is used to set the PID setting increase when drive is in fire mode control.
More details please see the description of parameter
F0.26
.