CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Eb.22
Range: 0.0~300.0
Default: 0.0
Any current
reaching 1
amplitude
Unit: %
This is a relative value to
b0.08
(motor rated current).
Please see the description of the following figure.
Eb.23
Range: 0.0~300.0
Default: 100.0
Any current
reaching 2
Unit: %
This is a relative value to
b0.08
(motor rated current).
If the output current of the AC drive is within the positive and negative
amplitudes of
Eb.23
*
b0.08
, the Y terminal allocated with function No.29
“Current 2 reached” becomes ON.
The any current detection function is shown in the following figure.
Eb.24
Range: 0.0~300.0
Default: 0.0
Any current
reaching 2
amplitude
Unit: %
This is a relative value to
b0.08
(motor rated current).
Please see the description of the following figure.
输出电流
时间
t
任意到达电流宽度
任意到达电流宽度
任意到达电流检测信号
Y
或继电器
ON
ON
ON
OFF
OFF
OFF
OFF
任意到达电流
Figure 6- 57 Any current reaching detection diagram
Eb.25
Range: 0.00~
Eb.26
Default: 3.70
AI1 input voltage
lower limit
Unit: V
Eb.25
and
Eb.26
are used to set the limits of the AI1 input voltage to
provide protection on the AC drive. When the AI1 input is smaller than the
value of
Eb.25
or larger than the value of
Eb.26
,the Y terminal allocated
with function No.31 “AI1 input limit exceeded” becomes ON.
Eb.26
Range:
Eb.25
~10.00
Default: 7.20
AI1 input voltage
upper limit
Unit: V
Please see the parameter description of
Eb.25
.
Note:
1mA equals to 0.5V when AI1 input signal is current type.
Eb.27
Range: - 40.0~125.0
Default: 100.0
Module
temperature
threshold
Unit:
℃
When the AC drive module heatsink temperature of the AC drive reaches
the value of this parameter,the Y terminal allocated with function No.17
“AC drive module temperature reached” becomes ON.