CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Setting
Function
Description
31 AI1 input limit exceeded
When the input voltage of AI1 is less than Eb.25(AI1 input voltage
lower limit), or greater than Eb.26(AI1 input voltage upper limit), the
terminal output ON signal.
32 Timing reached
Reference to
Eb.00
(
Timing function
)
,
Eb.01
(
Timing duration source
)
and
Eb.02
(
Timing duration
)
parameters’ description.
33 PLC cycle complete
When the PLC completes a run cycle, the terminal output a 250ms
width ON signal.
34 Current limit exceeded
Reference to
Eb.19
( Output over current threshold ),
Eb.20
( Output
over current detection delay time ) parameters’ description.
35 Communication setting
The terminal output state is set by communication, please reference to
chapter eight.
36 AI1>AI2
When the value of AI1 is bigger than AI2, the terminal output ON
signal, otherwise output OFF signal.
37
PID feedback Limit
exceeded
Please reference to the PID feedback measurement relevant
parameters description E5.30~E5.35
38
PID sleep status
indication
The terminal output ON signal when the PID in dormant sate. Please
reference to dormancy logic parameters description E5.38~E5.41
39 Frequency limited
When the AC drive set reference frequency exceeds the upper limit
frequency or below the lower limit frequency, and the output reaches
to the upper limit or lower limit frequency point, the terminal output
ON signal.
40 Motor 1# control output
Used to control motors ‘ switching in multi-pump system. More
detailed explanation, please reference to the description of group
E6(Multi pump control).
41 Motor 2# control output
42 Motor 3# control output
43
Motor 4# control output
44
External brake control
Please reference to the parameters’ description of group EA.
45
Simple brake control
Please reference to the par
ameters’ description of Eb.28~Eb.29.
C1.02
Range: 0~45
Default: 7
Y2 Function
Defines the functions of terminal Y2, same as C1.01.
C1.03
Range: 0~45
Default: 0
Y3 Function
Defines the functions of terminal Y3, same as C1.01.
C1.04
Range: 0~45
Default: 13
T1 Function
Defines the functions of rely T1, same as C1.01.
C1.05
Range: 0~45
Default: 0
T2 Function
Defines the functions of rely T2, same as C1.01.