CDE360 Vector Control AC Drive Chapter 6 Parameters Description
d0.23
①
Range: 0.0 ~ 100.0
Default: 100.0
Multi- point V/f
voltage 3
Unit: %
Multi-point V/f V3
When
V/f curve selection (d0.16)
is set to 1, output voltage characteristic is determined by
the settings of d0.17 ~ d0.23. 100% of voltage indicates motor rated voltage. See Fig6-D2
Note:
Multi-
point V/f curve’s setting must based on motor and load characteristic. Inappropriate
setting may cause motor damaged.
If motor 1 is active, 100% of voltage indicates motor 1 rated voltage.
If motor 2 is active, 100% of voltage indicates motor 2 rated voltage.
The relationship between voltages and frequencies is: V1
<
V2
<
V3,F1
<
F2
<
F3.
Output voltage
(
V
)
Motor rated voltage
Output frequency
(
Hz
)
0
d0.15 V0
f1
d0.16
d0.17 V1
f2
d0.18
d0.19 V2
f3
d0.20
d0.21 V3
Motor rated
frequency
Figure 6- 21 multi-point V/f curve
d0.24
Range: 0 ~ 8
Default: 0
Voltage source
for V/f separation
This parameter is valid when d0.14 is set to 7.
0: d0.25
1: AI1
2: AI2
3: AI3
(
optional card
)
4: X6/FI
5: PID. The output voltage is generated based on PID closed loop.
6: PLC. The voltage source is from simple PLC mode.
7: Multi-Reference. The voltage source is from multi-reference.
8: Communication
The output voltage is set by the host computer by means of
communication.
Note:
100.0% of the setting in each mode corresponds to the rated motor
except d0.25.
If a negative percentage is set, its absolute value is used instead.
The voltage source for V/F separation is set in the same way as the
frequency source.