CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group F1: Auto Reset
AC drive will auto reset after passing the time of
F1.01
when the fault happened.
If set F1.00 to 0 then the auto reset function invalid.
After the times of auto reset exceeds to
F1.00
, the AC drive will remain in the fault state. The
user can press STOP/RST key or X terminal(function 23) to reset the fault and clear the
accumulative time of auto reset.
F1.00
Range: 0~30
Default: 0
Fault auto reset
times
This defines the maximum times for auto reset. After trying this setting
times and the drive still fail to run, the AC drive will remain in the fault
state.
F1.01
Range: 0.1~100.0
Default: 1.0
Time interval of
fault auto reset
Unit: Sec
It is used to set the waiting time from the alarm of the AC drive to fault auto
reset.
F1.02
Range: 00~11
Default: 00
DO action during
fault auto reset
The unit’s digit of
F1.02
is used to decide whether the DO acts(function
13) during the fault auto reset if the fault auto reset function is selected.
The ten’s digit of
F1.02
is used to decide whether auto restart after the
fault is reset.
Unit's digit: Fault indication terminals
0: No action during fault reset process
1: Action during fault reset
Ten's digit: Restart after automatic fault reset
0: Not auto restart
1: having auto restart