Section 8. Operation
406
The absence of these design features causes significant error in the reference
junction temperature measurement.
If the CR6 must be used for thermocouple measurements, and those
measurements must be better than roughly 5 degrees in accuracy, an external
reference junction, such as a
multiplexer
(p. 652),
should be used. In addition, you
should carefully evaluate relevant parts of the
Thermocouple Measurements
section of the
CR1000 Datalogger Operator's Manual
, which is available at
www.campbellsci.com/manuals
.
On the other hand, the CR6 can make amazing thermocouple measurements if you
understands these limitations and work around them. Suggestions are:
•
Use an external charge regulator instead of the internal one.
•
Thermally insulate the enclosure and prevent air currents from changing
the wiring panel temperature
•
Use only one differential measurements and multiplex these through an
AM16/32B multiplexer, terminating the thermocouples on the
multiplexer and getting the reference temperature at the wiring panel of
the well insulated multiplexer.
8.1.2.3 Resistance Measurements — Details
Related Topics:
•
Resistance Measurements — Specifications
(p. 106)
•
Resistance Measurements — Overview
(p. 75)
•
Resistance Measurements — Details
(p. 406)
•
Measurement: RTD, PRT, PT100, PT1000
(p. 326)
By supplying a precise and known voltage to a resistive-bridge circuit and
measuring the returning voltage, resistance can be calculated.
CRBasic instructions for measuring resistance include:
BrHalf()
— half-bridge
BrHalf3W()
— three-wire half-bridge
BrHalf4W()
— four-wire half-bridge
BrFull()
— four-wire full-bridge
BrFull6W()
— six-wire full-bridge
Resistance()
— current-excitation resistance
Read More
Available resistive-bridge completion modules are listed in
Signal Conditioners — List
(p. 653).
The CR6 has six CRBasic bridge-measurement instructions. Table
Resistive-Bridge Circuits with Voltage Excitation shows ideal circuits and related
equations. In the diagrams, resistors labeled R
s
are normally the sensors and
those labeled R
f
are normally precision fixed (static) resistors. CRBasic example
Содержание CR6 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Страница 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Страница 136: ......
Страница 251: ...Section 7 Installation 251 FIGURE 46 Running Average Frequency Response FIGURE 47 Running Average Signal Attenuation ...
Страница 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Страница 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Страница 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Страница 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Страница 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Страница 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Страница 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Страница 542: ...Section 8 Operation 542 8 11 5 PCCard Memory Card Management FIGURE 128 CR1000KD PCCard Memory Card Management ...
Страница 546: ......
Страница 549: ...Section 9 Maintenance Details 549 FIGURE 133 Separate Back Shell from Module FIGURE 134 Disconnect Battery Connector ...
Страница 552: ......
Страница 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Страница 612: ......
Страница 648: ......
Страница 650: ......
Страница 688: ......
Страница 689: ......