Section 7. Installation
175
7.5.2.2
Operatin
g System (OS) — Details
The CR6 is shipped with the operating system pre-loaded. Check the pre-loaded
version by connecting your PC to the CR6 using the procedure outlined in
DevConfig Help
. OS version is displayed in the following location:
Deployment
tab →
Datalogger
tab →
OS Version
text box
Update the OS on the CR6 as directed in
DevConfig Help
. The current version of
the OS is found at
www.campbellsci.com/downloads
. OS updates are free of
charge.
Note
An OS file has a .obj extension.
Note the following precautions:
•
Since sending an OS resets CR6 memory, data loss will certainly occur.
Depending on several factors, the CR6 may also become incapacitated
for a time.
o
Is sending the OS necessary to correct a critical problem? If not,
consider waiting until a scheduled maintenance visit to the site.
o
Is the site conveniently accessible such that a site visit can be
undertaken to correct a problem of reset settings without excessive
expense?
o
If the OS must be sent, and the site is difficult or expensive to
access, try the OS download procedure on an identically
programmed, more conveniently located CR6.
•
Campbell Scientific recommends upgrading operating systems only with
a direct-hardwire link. However, the
Send Program
(p. 596)
button in the
datalogger support software
allows the OS to be sent over all software
supported comms systems.
o
Operating systems are very large files —
be cautious of line
charges
.
o
Updating the OS may reset CR6 settings, even settings critical to
supporting the comms link. Newer operating systems minimize this
risk.
The operating system is updated with one of the following tools:
7.5.2.2.1 OS Update with DevConfig Send OS Tab
Using this method results in the CR6 being restored to factory defaults. The
existing OS is over written as it is received. Failure to receive the complete new
OS will leave the CR6 in an unstable state. Use this method only with a direct
hardwire serial connection.
Содержание CR6 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Страница 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Страница 136: ......
Страница 251: ...Section 7 Installation 251 FIGURE 46 Running Average Frequency Response FIGURE 47 Running Average Signal Attenuation ...
Страница 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Страница 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Страница 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Страница 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Страница 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Страница 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Страница 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Страница 542: ...Section 8 Operation 542 8 11 5 PCCard Memory Card Management FIGURE 128 CR1000KD PCCard Memory Card Management ...
Страница 546: ......
Страница 549: ...Section 9 Maintenance Details 549 FIGURE 133 Separate Back Shell from Module FIGURE 134 Disconnect Battery Connector ...
Страница 552: ......
Страница 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Страница 612: ......
Страница 648: ......
Страница 650: ......
Страница 688: ......
Страница 689: ......