Section 7. Installation
310
An active sensor responds to each command. Responses have several standard
forms and terminate with <CR><LF> (carriage return–line feed).
SDI-12 commands and responses are defined by the SDI-12 Support Group
(www.sdi-12.org) and are summarized in the table
Standard SDI-12 Command &
Response Set
(p. 310).
Sensor manufacturers determine which commands to
support. The most common commands are detailed in the table
SDI-12
Commands for Transparent Mode
(p. 310).
SDI-12 Commands for Transparent Mode
Command Name
Command Syntax
1
Response
2
Notes
Break
Continuous
spacing for at least
12 milliseconds
None
Address Query
?!
a<CR><LF>
Acknowledge Active
a!
a<CR><LF>
Change Address
aAb!
b<CR><LF>
(support for this command is required only
if the sensor supports software changeable addresses)
Start Concurrent Measurement
aC!
atttnn<CR><LF>
Additional Concurrent
Measurements
aC1!
...
aC9!
atttnn<CR><LF>
Additional Concurrent
Measurements and Request
CRC
aCC1!
...
aCC9!
atttnn<CR><LF>
Send Data
aD0!
...
aD9!
a<values><CR><LF>
or
a<values><CRC><CR><LF>
Send Identification
aI!
allccccccccmmmmmmvvvxxx...xx<CR><LF>
. For
example,
013CampbellCS1234003STD.03.01
means
address = 0, SDI
-
12 protocol version number = 1.3,
manufacturer is Campbell Scientific, CS1234 is the
sensor model number (fictitious in this example), 003 is
the sensor version number, STD.03.01 indicates the
sensor revision number is .01.
Start Measurement
3
aM!
atttn<CR><LF>
Start Measurement and Request
CRC
3
aMC!
atttn<CR><LF>
Additional Measurements
3
aM1!
...
aM9!
atttn<CR><LF>
Additional Measurements and
Request CRC
3
aMC1!
...
aMC9!
atttn<CR><LF>
Continuous Measurements
aR0!
...
aR9!
a<values><CR><LF>
(formatted like the
D
commands)
Continuous Measurements and
Request CRC
aRC0!
...
aRC9!
a<values><CRC><CR><LF>
(formatted like the
D
commands)
Start Verification
3
aV!
atttn<CR><LF>
Содержание CR6 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Страница 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Страница 136: ......
Страница 251: ...Section 7 Installation 251 FIGURE 46 Running Average Frequency Response FIGURE 47 Running Average Signal Attenuation ...
Страница 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Страница 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Страница 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Страница 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Страница 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Страница 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Страница 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Страница 542: ...Section 8 Operation 542 8 11 5 PCCard Memory Card Management FIGURE 128 CR1000KD PCCard Memory Card Management ...
Страница 546: ......
Страница 549: ...Section 9 Maintenance Details 549 FIGURE 133 Separate Back Shell from Module FIGURE 134 Disconnect Battery Connector ...
Страница 552: ......
Страница 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Страница 612: ......
Страница 648: ......
Страница 650: ......
Страница 688: ......
Страница 689: ......