Section 7. Installation
282
software documentation available at
www.campbellsci.com
. Be aware of the
following precautions:
•
The CR6 does not check for out-of-bounds values in mode variables.
•
Valid mode variable entries are
1
or
4
.
Before, during, and after calibration, one of the following codes will be stored in
the
CalMode
variable:
FieldCal() Codes
Value Returned
State
-1
Error in the calibration setup
-2
Multiplier set to
0
or
NAN
; measurement =
NAN
-3
Reps
is set to a value other than
1
or the size of
MeasureVar
0
No calibration
1
Ready to calculate (
KnownVar
holds the first of a
two point calibration)
2
Working
3
First point done (only applicable for two point
calibrations)
4
Ready to calculate (
KnownVar
holds the second of a
two-point calibration)
5
Working (only applicable for two point calibrations)
6
Calibration complete
7.7.12.4.1 One-Point Calibrations (Zero or Offset)
Zero operation applies an offset of equal magnitude but opposite sign. For
example, when performing a zeroing operation on a measurement of 15.3, the
value –15.3 will be added to subsequent measurements.
Offset operation applies an offset of equal magnitude and same sign. For
example, when performing an offset operation on a measurement of 15.3, the
value 15.3 will be added to subsequent measurements.
See
FieldCal() Zero or Tare (Opt 0) Example
(p. 284)
and
FieldCal() Offset (Opt 1)
Example
(p. 286)
for demonstration programs:
1. Use a separate
FieldCal()
instruction and variables for each sensor to be
calibrated. In the CRBasic program , put the
FieldCal()
instruction
immediately below the associated measurement instruction.
2.
Set mode variable = 0 or 6 before starting.
3. Place the sensor into zeroing or offset condition.
Содержание CR6 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Страница 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Страница 136: ......
Страница 251: ...Section 7 Installation 251 FIGURE 46 Running Average Frequency Response FIGURE 47 Running Average Signal Attenuation ...
Страница 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Страница 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Страница 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Страница 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Страница 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Страница 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Страница 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Страница 542: ...Section 8 Operation 542 8 11 5 PCCard Memory Card Management FIGURE 128 CR1000KD PCCard Memory Card Management ...
Страница 546: ......
Страница 549: ...Section 9 Maintenance Details 549 FIGURE 133 Separate Back Shell from Module FIGURE 134 Disconnect Battery Connector ...
Страница 552: ......
Страница 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Страница 612: ......
Страница 648: ......
Страница 650: ......
Страница 688: ......
Страница 689: ......