Section 7. Installation
308
'Excite - delay 1 second - differential measurement:
ExciteV
(U12,2500,0)
'<<<<Note: Delay = 0
Delay
(0,1000,mSec)
VoltDiff
(VoltageDIFF,1,mV5000,U3,True,0,15000,1.0,0)
'Write data to final-data memory
CallTable
Voltage
NextScan
EndProg
7.7.15 Serial I/O: SDI-12 Sensor Support — Details
Related Topics:
•
SDI-12 Sensor Support — Overview
(p. 83)
•
SDI-12 Sensor Support — Details
(p. 469)
•
Serial I/O: SDI-12 Sensor Support — Programming Resource
(p. 308)
See the table
CR6 Terminal Definitions
(p. 62)
for
U
and
C
terminal assignments for
SDI-12 input. Multiple SDI-12 sensors can be connected to each configured
terminal. If multiple sensors are wired to a single terminal, each sensor must have
a unique address. SDI-12 standard v 1.3 sensors accept addresses
0
through
9
,
a
through
z
, and
A
through
Z
. For a CRBasic programming example demonstrating
the changing of an SDI-12 address on the fly, see Campbell Scientific publication
PS200/CH200 12 V Charging Regulators
, which is available at
www.campbellsci.com
.
The CR6 supports SDI-12 communication through two modes — transparent
mode and programmed mode.
•
Transparent mode facilitates sensor setup and troubleshooting. It allows
commands to be manually issued and the full sensor response viewed.
Transparent mode does not record data.
•
Programmed mode automates much of the SDI-12 protocol and provides
for data recording.
7.7.15.1 SDI-12 Transparent Mode
System operators can manually interrogate and enter settings in probes using
transparent mode. Transparent mode is useful in troubleshooting SDI-12 systems
because it allows direct communication with probes.
Transparent mode may need to wait for commands issued by the programmed
mode to finish before sending responses. While in transparent mode, CR6
programs may not execute. CR6 security may need to be unlocked before
transparent mode can be activated.
Transparent mode is entered while the PC is in comms with the CR6 through a
terminal emulator program. It is easily accessed through a terminal emulator.
Campbell Scientific DevConfig program has a terminal utility, as to other
datalogger support software
(p. 97).
Keyboard displays cannot be used.
Содержание CR6 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 36: ......
Страница 38: ......
Страница 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Страница 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Страница 136: ......
Страница 251: ...Section 7 Installation 251 FIGURE 46 Running Average Frequency Response FIGURE 47 Running Average Signal Attenuation ...
Страница 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Страница 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Страница 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Страница 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Страница 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Страница 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Страница 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Страница 542: ...Section 8 Operation 542 8 11 5 PCCard Memory Card Management FIGURE 128 CR1000KD PCCard Memory Card Management ...
Страница 546: ......
Страница 549: ...Section 9 Maintenance Details 549 FIGURE 133 Separate Back Shell from Module FIGURE 134 Disconnect Battery Connector ...
Страница 552: ......
Страница 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Страница 612: ......
Страница 648: ......
Страница 650: ......
Страница 688: ......
Страница 689: ......