S-Series Technical Manual
77
Cambridge Air Solutions
OPERATING SEQUENCES
UNIT HEATER / OCCUPIED MODE
1. If Zone Temperature is below Zone Set Point
then Supply Fan and Burner start.
2. Discharge Temperature modulates to
Discharge Set Point.
3. If Zone Temperature is above Zone Set Point
plus Differential then Supply Fan and Burner
stop.
4. Unit will not operate if Outdoor Temperature
is above Heating Lockout Set Point.
MAKEUP AIR / OCCUPIED MODE
1. Supply Fan and Burner run continuously.
2. Discharge Temperature modulates to
Discharge Set Point.
3. Burner will not operate if Outdoor
Temperature is above Heating Lockout Set
Point.
MAKEUP AIR w/PID / OCCUPIED MODE
1. Supply Fan and Burner run continuously.
2. Discharge Temperature modulates to
Discharge Set Point based on PID loop.
3. Burner will not operate if Outdoor
Temperature is above Heating Lockout Set
Point.
MAKEUP AIR w/PID PLUS ON-OFF /
OCCUPIED MODE
1. If Zone Temperature is below Zone Set Point
plus Differential then Supply Fan and Burner
start.
2. Discharge Temperature modulates to
Discharge Set Point based on PID loop.
3. If Zone Temperature is above Zone Set Point
plus Differential then Supply Fan and Burner
stop.
4. Burner will not operate if Outdoor
Temperature is above Heating Lockout Set
Point.
SUMMER VENTILATION MODE
1. If Zone Temperature (AI8) is above Zone Set
Point (AV4) then Supply Fan (BO1) starts.
2. If Zone Temperature (AI8) is below Zone Set
Point (AV4) minus Differential (AV28) then
Supply Fan (BO1) stops.
3. Supply Fan (BO1) will not operate if
Outdoor Temperature (AV20) is above Zone
Temperature (AI8).
UNOCCUPIED MODE
1. If Zone Temperature is below Zone Set Point
then start Supply Fan and Burner.
2. Discharge Temperature modulates to
Discharge Set Point.
3. If Zone Temperature is above Zone Set Point
plus Differential then stop Supply Fan and
Burner.
4. Unit will not operate if Outdoor Temperature
is above Heating Lockout Set Point.
DEFAULT SETTINGS
The controller will function to control the unit without
the network being connected, provided that a Zone
Temperature Sensor is connected.
The default settings are:
• Normal Mode = Unit Heater
• Discharge Set Point = 160°F
• Zone Set Point = 65°F
• Set Point Differential = 3°F
Содержание S Series
Страница 93: ...S Series Technical Manual 91 Cambridge Air Solutions REFERENCE ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING ...
Страница 100: ...Cambridge Air Solutions 98 S Series Technical Manual REFERENCE BUILDING AUTOMATION SYSTEM ...
Страница 112: ...Cambridge Air Solutions 110 S Series Technical Manual MAINTENANCE LOG MODEL NO SERIAL NO Date Activity Technician ...
Страница 113: ...MAINTENANCE LOG MODEL NO SERIAL NO Date Activity Technician ...
Страница 114: ...Cambridge Air Solutions 112 S Series Technical Manual ...
Страница 116: ...760 Long Road Crossing Dr Chesterfield MO 63005 Phone 636 532 2233 800 899 1989 Fax 636 530 6133 www cambridgeair com ...