S-Series Technical Manual
65
Cambridge Air Solutions
SETTING TEMPERATURES
The Operating Electronic Thermostat requires two
temperature settings. When the temperature drops below
the HEAT ON setting, the heater will turn on. When
the heater raises the space temperature above the HEAT
OFF setting, the heater will turn off. This difference
provides an adjustable range of operation for the heater
which minimizes temperature swings.
The minimum run time and off time for the heater
regardless of temperature are both set at 2 minutes. The
allowable temperature range is 40°F to 99°F. The HEAT
OFF temperature can not be set lower than the HEAT
ON temperature.
1. Press and hold the
HEAT ON
button while pressing
the
UP
or the
DOWN
button until the desired
temperature for the heater to turn ON is displayed.
2. Press and hold the
HEAT OFF
button while pressing
the
UP
or the
DOWN
button until the desired
temperature for the heater to turn OFF is displayed.
TEMPERATURE CALIBRATION
To compensate for lead wire resistance, it may be
necessary to make an adjustment to the displayed
temperature to correct it to the temperature measured at
the thermistor sensor. The calibration feature allows the
displayed temperature to be offset either above or below
the actual sensed temperature. Be sure to use an accurate
temperature meter for making this correction.
1. Press and hold the
HEAT ON
and
HEAT OFF
buttons
while pressing the
UP
or the
DOWN
button until the
correct temperature is displayed. ( A period [.] after
the temperature will indicate the Calibration Mode).
2. Pressing the
UP
or the
DOWN
button will display the
current calibration difference above or below (-) the
measured temperature.
Содержание S Series
Страница 93: ...S Series Technical Manual 91 Cambridge Air Solutions REFERENCE ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING ...
Страница 100: ...Cambridge Air Solutions 98 S Series Technical Manual REFERENCE BUILDING AUTOMATION SYSTEM ...
Страница 112: ...Cambridge Air Solutions 110 S Series Technical Manual MAINTENANCE LOG MODEL NO SERIAL NO Date Activity Technician ...
Страница 113: ...MAINTENANCE LOG MODEL NO SERIAL NO Date Activity Technician ...
Страница 114: ...Cambridge Air Solutions 112 S Series Technical Manual ...
Страница 116: ...760 Long Road Crossing Dr Chesterfield MO 63005 Phone 636 532 2233 800 899 1989 Fax 636 530 6133 www cambridgeair com ...