34
APPENDIX 2 - REPORTING IN CONTACT ID
The 7600 has the ability to report Ademco Contact ID transmissions to either or both phone numbers. Each report
in Contact ID consists of an Event Code and a Zone or User ID. The Zone is programmed in the first digit of each
report. When programming the event code (the second digit) for zones 1-6 (locations 105, 107, 109, 111, 113, or
115), programming a zero will cause the event code to follow the zone type for that zone. The event code for the
zone type can be overridden by programming a digit from the table below. Duress (location 87), AUX 1 (location 89),
AUX 2 (location 91), and Keypad Panic (location 93) must be programmed from the table below.
Programmed Event Code
Contact ID Code
Description
1
110
Fire Alarm
2
122
Panic alarm
3
130
Burglary Alarm
4
131
Perimeter Alarm
5
132
Interior Alarm
6
133
24 Hour Burglary
7
134
Entry Alarm
8
135
Day/Night Alarm
9
150
Non-Burglary 24 Hour
10
121
Duress Alarm
11
100
Medical Alarm
12
123
Audible Panic Alarm
13
137
Tamper Alarm
14
602
Periodic Test
15
300
System Fault
The following reports will send fixed event codes regardless of the number programmed in the event code location:
Event
Contact ID Code
Event Code Location
Keypad Tamper
137
95
Download Complete
412
97
Autotest
602
99
Fail to Communicate
354
101
Closing
401
102
Opening
401
103
Start Test/End Test
607
116
AC Loss
301
121
Low Battery
302
123
Trouble
380
124
Bypass
570
125
Restore
*
126
Cancel
406
127
Exit Error
138
210
Recent Closing
401
211
Auxiliary 3
140
253
User on site
605
254
* This will send the event code for the zone restored.