17
LOCATION 140: PRIORITY SIREN CUTOFF INHIBIT
If a “1" is programmed in location 140, a Priority zone type siren will sound continuously until an arm/disarm code
is entered. If this location contains a “0", the Priority zone type siren will shutdown after the amount of time
programmed in location 077 has elapsed. Programming in this location does not affect the burglary siren.
LOCATION 141: PROGRAMMING LOCAL SYSTEM FUNCTIONS
Location 141 is used to enable the exit warning tone and the missing battery test. The exit warning tone sounds a
long beep followed by 3 short beeps, 10 seconds before the exit delay expires. To enable the exit warning, program
a "1" in location 141. Location 141 is also used to enable the missing battery test. When enabled this feature will
cause the system to test the standby battery once every 40 seconds to see if it is present. If it is not, a low battery
will be detected. To enable missing battery detection program a "2" in location 141. To enable both exit warning and
missing battery detection program a "3".
LOCATION 142: SIREN/BELL TEST FEATURE
The siren/bell can be programmed to activate upon different conditions. Using the chart below, add the values of
the desired condition(s) and program the sum of those values in location 142. When the siren/bell is activated by
pressing the [1] and [7] keys simultaneously, the communicator will not report a message, the siren/bell will be
activated and a 1 minute battery test will begin. The bell/siren can be silenced by entering an arm/disarm code.
VALUE
DESCRIPTION
1
Activation by pressing [1] and [7] keys simultaneously
2
Momentary activation at arming
4
Momentary at end of exit delay
8
Momentary at kiss off ringback
LOCATION 143: SMOKE POWER RESET AND/OR FIRE ALARM VERIFICATION
Programming a "1" in location 143 will cause the 7600 (when in the disarmed state) to interrupt the smoke detector
power each time the [#] button is pressed. If this location contains a "0", the smoke detector power will reset only
after the [#] button is pressed when the corresponding LED(s) for zones designated as "Priority" are on steady for
alarm or blinking for trouble. Programming a "2" in this location will enable the "Fire Alarm Verification" feature. When
the "Fire Alarm Verification" feature is enabled, a smoke detector will be powered down and reset automatically after
the first trip, waiting for a second trip within a 2 minute time frame (thus verifying a fire alarm condition) before
creating an alarm and communicating a message.
LOCATION 144: RESERVED