LOCATION

PAGE

DESCRIPTION

ZONE ID

EVENT/EXT CODE

DEFAULT

102

13

CLOSING COMMUNICATOR CODE

MAN NUMBER

"0" DISABLED

103

13

OPENING COMMUNICATOR CODE

MAN NUMBER

"0" DISABLED

104-105

13

ZONE 1 COMMUNICATOR CODE

"1 - 0"

106-107

13

ZONE 2 COMMUNICATOR CODE

"2 - 0"

108-109

13

ZONE 3 COMMUNICATOR CODE

"3 - 0"

110-111

14

ZONE 4 COMMUNICATOR CODE

"4 - 0"

112-113

14

ZONE 5 COMMUNICATOR CODE

"5 - 0"

114-115

14

ZONE 6 COMMUNICATOR CODE

"6 - 0"

116-117

14

START TEST COMMUNICATOR CODE

"0 - 0" DISABLED

118-119

14

END TEST COMMUNICATOR CODE

"0 - 0" DISABLED

120-121

14

AC POWER LOSS COMMUNICATOR CODE

"0" DISABLED

122-123

14

LOW BATTERY COMMUNICATOR CODE

"0" DISABLED

124

15

TROUBLE COMMUNICATOR CODE

ZONE NUMBER

"0" DISABLED

125

15

ZONE BYPASS COMMUNICATOR CODE

ZONE NUMBER

"0" DISABLED

126

15

RESTORE COMMUNICATOR CODE

ZONE NUMBER

"0" DISABLED

127

15

CANCEL COMMUNICATOR CODE

MAN NUMBER

"0" DISABLED

LOCATION

PAGE

DESCRIPTION

DATA

DEFAULT

128

15

ABORT DELAY BEFORE DIAL TIME

"0" DISABLED

129

15

KEYPAD PANIC SILENT OR AUDIBLE

"0" AUDIBLE

130

15

LIMITED SIREN AND/OR COMMUNICATOR OUTPUTS

"0" UNLIMITED

131

16

AUTO BYPASS / INSTANT ARMING

"0" DISABLED

132

16

ENABLE KEYPAD SIREN SOUNDER         (8001 KEYPAD ONLY)

"0" DISABLED

133

16

LED EXTINGUISH FEATURE

"0" DISABLED

134

16

NUMBER OF DIAL ATTEMPTS

"8" EIGHT

135

16

POWER UP CONDITION

"0" LAST

136

16

POWER UP DELAY

"0" 60 SEC DELAY

137

16

IMMEDIATE RESTORE BY ZONE

"0" DISABLED

138

16

NO ARMING WITH ZONE BYPASSED

"0" DISABLED

139

17

QUICK ARM ENABLE

"0" DISABLED

140

17

FIRE SIREN CUTOFF INHIBIT

"0" RECYCLES

141

17

EXIT WARNING ENABLE (BATTERY TEST -DISABLED)

‘1" ENABLED

142

17

SIREN/BELL TEST FEATURE

"0" DISABLED

143

17

SMOKE POWER RESET AND/OR FIRE ALARM VERIFICATION

"1" POWER RESET

144

17

RESERVED

RESERVED

145

17

AUXILIARY OUTPUT CONDITION #1

"14" 

146

17

AUXILIARY OUTPUT CONDITION #2

"0" 

147

17

AUXILIARY OUTPUT CONDITION #3

"0" 

148

17

AUXILIARY OUTPUT CONDITION #4

"0" 

149

18

INVERTING THE AUXILIARY OUTPUT

"0" HI  GOING LOW

150

18

DELAY AC POWER LOSS  REPORT

"5 “ = 10 MINUTES

151

18

NUMBER OF RINGS TO ANSWER DOWNLOAD CALL

"0" 

152

19

NUMBER OF DAYS LEFT UNTIL AUTOTEST

UNDEFINED

Содержание RANGER 7600

Страница 1: ...RAM THE RANGER 7600 6 KEYPAD PROGRAMMING EXAMPLES 7 OPTIONAL 8950 PROGRAMMER EXAMPLE 7 PROGRAMMING INSTRUCTIONS 8 28 PROGRAMMING WORKSHEETS 29 32 APPENDIX 1 33 APPENDIX 2 34 LOCAL TELEPHONE COMPANY IN...

Страница 2: ...s Read the USER S MANUAL before you begin the installation for the best overall description of how the Ranger 7600 functions After installation of the security system complete the information on page...

Страница 3: ...duration at 6 00 AM Page 22 Location 203 ENTRY GUARD This unique low level arming mode has been developed to reduce the most common source of false alarms When armed in this mode the opening of any z...

Страница 4: ...4 TERMINAL DRAWING SPECIAL NOTES...

Страница 5: ...OOP 8 Connect one side of zone 6 loop The other side of loop to common terminal 6 Open only causes alarm DO NOT USE 3 3K EOL RESISTOR ON THIS LOOP 9 10 Auxiliary power regulated 12VDC 500 mA maximum 1...

Страница 6: ...9 7 1 3 NOTE The 7600 must be disarmed to gain access to programming with this code After entry of this code the 7600 will be in the Program mode and the yellow LED s will display the data in locatio...

Страница 7: ...7...

Страница 8: ...l 4 2 program a 1 in location 052 Contact ID requires a 13 in this location If you need another format choose from those listed in the format table located on the following page and program the data i...

Страница 9: ...FAST 1800HZ TRANSMIT 2300HZ 20PPS 5 EXTENDED RADIONICS SLOW 1800HZ TRANSMIT 2300HZ HANDSHAKE DOUBLE ROUND PARITY 20 PPS EXTENDED HEX CAPABILITY 6 EXTENDED RADIONICS SLOW 1800HZ TRANSMIT 1400HZ HANDSH...

Страница 10: ...th the Ranger 7600 disarmed the Go To Program access code can be used to enter the program mode To disable the Go To Program access code program a 15 in location 028 The factory default setting is 9 7...

Страница 11: ...ode then pressing r 6 INSTANT Produces an instant alarm when tripped in the armed mode ignored when disarmed 7 24 HOUR SILENT A trip on a 24 hour silent zone will communicate to the central station wh...

Страница 12: ...aneously on the keypad The desired Auxiliary 2 code is programmed in locations 090 091 If both locations are 0 the Auxiliary 2 double keypress is disabled Location 090 contains the standard digit and...

Страница 13: ...in Location 102 If this location contains a 0 closing will not be reported When using a one button Quick Arm code or the Remote Arming input the man number is 1 When using the Auto Arm feature the man...

Страница 14: ...16 contains the standard digit and location 117 contains the extended digit When Contact ID is selected program the extended or the second location with any number to activate LOCATION 118 119 PROGRAM...

Страница 15: ...nicator code that will be sent for cancel The cancel code programmed in this location will be sent if an arm disarm code is entered after a trip on zones 1 through 6 has been reported excluding 24 hou...

Страница 16: ...ion process If this location contains an 8 the communicator will make 8 attempts to the first number and then eight attempts to a second number if a second number is programmed as backup LOCATION 135...

Страница 17: ...the chart below add the values of the desired condition s and program the sum of those values in location 142 When the siren bell is activated by pressing the 1 and 7 keys simultaneously the communic...

Страница 18: ...MOMENTARY OUTPUT 8 TAMPER ALARM LATCHED OUTPUT 9 AUTOTEST MOMENTARY OUTPUT 10 RESERVED NOT USED 11 ALARM MEMORY LATCHED OUTPUT 12 ENTRY LATCHED OUTPUT 13 EXIT LATCHED OUTPUT 14 SMOKE DETECTOR POWER L...

Страница 19: ...n should contain a 6 which is the ones digit of the current year LOCATION 156 PROGRAMMING THE CLOCK CURRENT DAY OF THE MONTH TENS DIGIT Location 156 contains the current day of the month tens digit If...

Страница 20: ...e desired autotest time is 9 36 AM the 24 hour time is 09 36 and this location should contain a 9 LOCATION 164 PROGRAMMING THE AUTOTEST TIME MINUTES TENS DIGIT Location 164 contains the tens digit of...

Страница 21: ...sed to send alarm reports to one number and supervisory reports to another number When using split reporting with the 7600 the primary telephone number always takes priority over the secondary number...

Страница 22: ...rmat options as follows VALUE DESCRIPTION 1 Add for extended reporting 2 Add for hex digits allowed 4 Add for 20PPS 8 Add for 10PPS LOCATION 183 FORMAT OVER RIDE LOCATION The number selected in this l...

Страница 23: ...secure will become armed Factory default is 0 Force Arming disabled LOCATIONS 198 201 AUTOMATIC ARMING TIME Locations 198 201 contain the time for automatic arming if enabled in location 202 Enter the...

Страница 24: ...OTEST E 14 LOCATION 205 DUAL REPORTING PROGRAMMING AC POWER FAIL LOW BATTERY AND OPEN CLOSE TO REPORT TO THE PRIMARY AND SECONDARY PHONE NUMBERS The 7600 is capable of sending certain reports to both...

Страница 25: ...t options as follows VALUE DESCRIPTION 1 Add for Contact ID 2 Add for SIA 4 Add for 4 3 8 Add for DTMF transmission LOCATION 210 PROGRAMMING TO REPORT EXIT ERROR The Ranger 7600 has the ability to rep...

Страница 26: ...rt VALUE DESCRIPTION 1 Cross Zone 2 Entry Guard Zone 4 Group Bypass Zone 8 Trouble Reporting CROSS ZONING This feature requires a trip on 2 or more zones programmed as Cross Zones within the time fram...

Страница 27: ...by entering r 0 followed by a valid arm disarm code at the keypad when the system is not armed This can be used to log the return of latch key kids or the presence of employees The desired user on si...

Страница 28: ...l comes in during that 45 second time frame the control panel will answer on the first ring To disable this feature program a 0 in this location LOCATION 281 LOCAL PROGRAMMING LOCKOUT Location 281 is...

Страница 29: ...0 073 9 SECONDARY ACCOUNT CODE 0 DISABLED 074 9 SECONDARY FORMAT 0 DISABLED CONTROL COMMUNICATOR FEATURES LOCATION PAGE DESCRIPTION DATA DEFAULT 075 10 ENTRY DELAY TIME 10 SECOND INCREMENTS 3 30 SECON...

Страница 30: ...E DIAL TIME 0 DISABLED 129 15 KEYPAD PANIC SILENT OR AUDIBLE 0 AUDIBLE 130 15 LIMITED SIREN AND OR COMMUNICATOR OUTPUTS 0 UNLIMITED 131 16 AUTO BYPASS INSTANT ARMING 0 DISABLED 132 16 ENABLE KEYPAD SI...

Страница 31: ...ONE 1 177 20 SPLIT REPORTING AC FAILURE LOW BAT OPEN CLOSE 0 PHONE 1 178 20 SECONDARY ENTRY DELAY TIME 0 179 21 SECONDARY EXIT DELAY TIME 0 180 21 LOOP RESPONSE TIME 0 500 MS 181 21 AUTOTEST SUPPRESSI...

Страница 32: ...8 245 25 ZONE 2 SPECIAL CHARACTERISTICS 8 246 25 ZONE 3 SPECIAL CHARACTERISTICS 8 247 25 ZONE 4 SPECIAL CHARACTERISTICS 8 248 25 ZONE 5 SPECIAL CHARACTERISTICS 8 249 25 ZONE 6 SPECIAL CHARACTERISTICS...

Страница 33: ...ent SIA Code Description 1 FA Fire Alarm 2 PA Panic alarm 3 BA Burglary Alarm 4 GA Gas Alarm 5 KA Heat Alarm 6 WA Water Alarm 7 QA Emergency Alarm 8 SA Sprinkler Alarm 9 UA Untyped Alarm 10 HA Holdup...

Страница 34: ...Code Contact ID Code Description 1 110 Fire Alarm 2 122 Panic alarm 3 130 Burglary Alarm 4 131 Perimeter Alarm 5 132 Interior Alarm 6 133 24 Hour Burglary 7 134 Entry Alarm 8 135 Day Night Alarm 9 15...

Страница 35: ...rect the situation The customer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES The telephone com...

Страница 36: ...36 NOTES...

Страница 37: ...INSIDE BACK COVER IS BLANK...

Страница 38: ...G IF ANY DEFECT APPEARS DURING THE WARRANTY PERIOD RETURN IT TO CADDX POSTAGE PREPAID THE UNIT WILL BE REPAIRED AND RETURNED FOR THE REMAINING 36 MONTHS OF WARRANTY THE UNIT WILL BE REPAIRED FOR A FEE...

Отзывы: