11
LOCATIONS 078-083: PROGRAMMING THE ZONE TYPES
Locations 078 through 083 contain a number identifying the characteristics of each of the 6 zones. Location 078
corresponds to zone 1 and location 083 corresponds to zone 6. Each zone will factory default according to the
programming worksheet. To program zone characteristics other than the default values, program a number from "1"
to "10" based on the characteristics in the list below. NOTE: Zones 5 and 6 cannot be Priority (FIRE) zones.
NUMBER
ZONE CHARACTERISTICS DESCRIPTION
"1"
DAY ZONE
- A trip on a Day zone will produce an instant alarm when armed, and activate the keypad
sounder when disarmed.
"2"
24 HOUR -
A trip on a 24 Hour zone will produce an instant alarm when armed or disarmed.
"3"
ENTRY/EXIT
- A trip will start entry delay. The lack of a trip during exit delay will enable the "Automatic
Bypass" or "Instant" mode if so programmed.
"4"
INTERIOR DELAY
- A trip on Interior Delay zone will initiate an entry delay. It will be ignored during exit
delay and when disarmed .
"5"
INTERIOR FOLLOWER
-
Interior zone that follows delay zones. It can be bypassed before arming, or
automatically bypassed in the "Automatic Bypass/Instant" mode if so programmed. When bypassed, it can
be reactivated by entering first digit of User 1 code then pressing [
r
].
"6"
INSTANT
- Produces an instant alarm when tripped in the armed mode, ignored when disarmed.
"7"
24 HOUR SILENT
- A trip on a 24 hour silent zone will communicate to the central station when the Ranger
7600 is armed or disarmed.
"8"
PRIORITY
- A short on a Priority zone (non-bypassable) will communicate to the central station when the
Ranger 7600 is armed or disarmed. An open will create a Trouble condition. Keypad LED will be steady
for FIRE, and flashing for Trouble. Only Zones 1-4 can be used as Priority.
“9"
SECONDARY DELAY
- A secondary delay zone works like an entry/exit zone but has its own
independent delay time (see locations 178-179).
“10"
24 HOUR -
A trip on a 24 Hour zone will produce a beeping keypad when armed or disarmed.
LOCATION 084: PROGRAMMING THE ZONE 1-4 SIREN SELECT
Location 84 is used to select the Siren for zones 1-4. Refer to the chart below to choose the zone(s) for siren
activation. Add the values of the zones selected and program the sum in location 084.
VALUE
DESCRIPTION
1
Zone 1
2
Zone 2
4
Zone 3
8
Zone 4
Example: If zones 2 & 3 are to sound the siren for an alarm, program a "6". Factory default is “15", all zones initiate
a siren.
LOCATION 085: PROGRAMMING THE ZONE 5-6 SIREN SELECT
Location 85 is used to select the Siren for zones 5-6. Refer to the chart below to choose the zone(s) for siren
activation. Add the values of the zones selected and program the sum in location 085. Default is “3".
VALUE
DESCRIPTION
1
Zone 5
2
Zone 6