ALARM REPORTING
Check for Alarms
If alarms are present when you first dial in to your site, the Voice Interface will connect to the first unit with
alarms, and then report those alarms, beginning with the oldest. After the initial connection, check alarms on the
current I/O unit by entering 000. The Voice Interface will look for alarms, and if there are any, the unit will enter
Alarm Reporting and announce the first pending alarm.
Use the following commands to navigate through Alarm Reporting:
Clearing Alarms
To clear all the alarms stored on the Voice Interface unit, enter 010. A cleared alarm will not be reported again
until the channel returns to its normal condition and the alarm state recurs.
Clearing an alarm does not affect any channel conditions; it simply removes the alarm from the Voice Interface.
It will remain on the Alarm List in Lynx, and it will appear in the site log. However, once you clear alarms, they
cannot be restored.
Suspending Alarm Dial-Out
If you want the Voice Interface to stop dialing, but also keep the alarm active, you can suspend alarm reporting
for any or all telephone numbers.
Enter 0
03
30
0** to disable alarm reporting on all telephone numbers for a one-hour period. This is also useful if you
will be disconnecting equipment to perform maintenance and do not want alarms reported to station personnel
during the maintenance period. After one hour, alarm reporting will be automatically restored. You can manually
enable it prior to that time by entering 0
03
30
0#
#.
If you would like to indefinitely disable alarm reporting for specific phone numbers, enter 1
10
0 __ **, where the blank
represents a telephone number entry (1-5) in the unit’s site dialing settings.
E
Exxa
am
mp
plle
e
The Voice Interface will not dial this phone number until you enter 1
10
0 __ #
# to resume alarm reporting for that
entry. You can disable alarm reporting for as many phone numbers as you wish.
CHAPTER 11: VOICE INTERFACE OPERATION
115
CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.com
A
Alla
arrm
m R
Re
ep
po
orrttiin
ng
g A
Accttiio
on
nss
#
Step forward to next alarm
*
Step back to previous alarm
8
Repeat last alarm
6*
Report security mode (Operator / Observer)
3 (or 0#)
Exit Alarm Reporting
010
Clear alarms on all units and exit
IIn
np
pu
utt::
103*
R
Re
essp
po
on
nsse
e:: Phone number 3 disabled
Содержание GSC3000
Страница 8: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL viii ...
Страница 22: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 14 ...
Страница 32: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 24 ...
Страница 40: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 32 ...
Страница 52: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 44 ...
Страница 61: ...CHAPTER 6 MODEM SITE EQUIPMENT CONNECTIONS 53 CUSTOMER SUPPORT 978 486 3711 support burk com www burk com ...
Страница 68: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 60 ...
Страница 120: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 112 ...
Страница 128: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 120 ...
Страница 132: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 124 ...
Страница 140: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 132 ...
Страница 144: ...GSC3000 VRC2500 INSTALLATION OPERATION MANUAL 136 ...