11.1.2
Switching off
Damage to the supply unit!
NOTICE
At regenerative supply units, at least 10 ms have to elapse between the
mains OFF request and the disconnection of the mains voltage, so that the
energy flow has been interrupted when the disconnection process starts.
You can make sure this order is observed by appropriate switch elements
(e.g., by a control cabinet main switch with leading auxiliary contact). For this
purpose, connect the auxiliary contact in series with mains OFF.
t1
Time depends on device (mains contactor off delay); OFF re‐
lates to the hardware input
Fig. 11-2:
Signal sequences when switching off
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
370/407
Rexroth IndraDrive ML Drive Systems with HMU05
Appendix
Содержание Rexroth HMU05.1N Series
Страница 1: ...Rexroth IndraDrive ML Drive Systems with HMU05 Project Planning Manual R911344279 Edition 02 ...
Страница 12: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P X 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 32: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 30 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 46: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 44 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 124: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 122 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 138: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 136 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 366: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 364 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 370: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 368 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 409: ...Notes DOK INDRV HXX05 PR02 EN P Bosch Rexroth AG 407 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...