Guide value "Rise of voltage at output"
Note that the load on the motor is virtually independent of the
power section used.
When using standard motors in particular, make sure they can
handle the voltage load.
Reduced output current at motor standstill
Depending on the electric output frequency, the output current is
reduced for thermal protection of the power section.
The output current is reduced, when the electric output frequency
has fallen below the threshold to detect motor standstill.
For the highest possible acceleration, the maximum current I
max
may not flow
for more than 400 mss every 10 minutes.
Fig. 7-1:
Current profile during acceleration
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
146/407
Rexroth IndraDrive ML Drive Systems with HMU05
Technical data of the components
Содержание Rexroth HMU05.1N Series
Страница 1: ...Rexroth IndraDrive ML Drive Systems with HMU05 Project Planning Manual R911344279 Edition 02 ...
Страница 12: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P X 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 32: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 30 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 46: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 44 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 124: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 122 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 138: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 136 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 366: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 364 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 370: ...Bosch Rexroth AG DOK INDRV HXX05 PR02 EN P 368 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...
Страница 409: ...Notes DOK INDRV HXX05 PR02 EN P Bosch Rexroth AG 407 407 Rexroth IndraDrive ML Drive Systems with HMU05 ...