Product overview
CX1500-M510, CX1500-B510
42
Version: 1.0
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1803
0
Number of
elements
Unsigned8 ro
N
5
Communica
tion
parameters
for the
fourth
transmit
PDO. Sub-
index 0:
number of
following
parameters
1
COB-ID
Unsigned32 rw
N
0x0000048
0 + Node-
ID
COB-ID
(Communic
ation Object
Identifier)
TxPDO1
2
Transmissi
on Type
Unsigned8 rw
N
255
Transmissi
on type of
the PDO
3
Inhibit Time Unsigned16 rw
N
0
Repetition
delay [value
x 100 µs]
4
CMS
Priority
Group
Unsigned8 rw
N
-
Present for
reasons of
backwards
compatibilit
y, but not
used.
5
Event
Timer
Unsigned16 rw
N
0
Event-
Timer
The fourth transmit PDO contains analog input data as a rule (see
). It is configured for
event-driven transmission (transmission type 255). Event-driven mode must first be activated (see object
0x6423), otherwise the inputs can only be interrogated (polled) by remote transmission request (RTR).