Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1404 -
0x140F
(dependin
g on the
device
type)
0
Number of
elements
Unsigned8 ro
N
5
Communica
tion
parameter
for the 5
th
to
16
th
receive
PDOs.
1dth="5%">
1
COB-ID
Unsigned32 rw
N
0x8000000 COB-ID
(Communic
ation Object
Identifier)
RxPDO5...1
6
2
Transmissi
on Type
Unsigned8 rw
N
255
Transmissi
on type of
the PDO
3
Inhibit Time Unsigned16 rw
N
0
Present for
reasons of
backwards
compatibilit
y, but not
used in the
RxPDO.
4
CMS
Priority
Group
Unsigned8 rw
N
-
Present for
reasons of
backwards
compatibilit
y, but not
used.
5
Event
Timer
Unsigned16 rw
N
0
Event-
Timer.
Watchdog
time
defined for
monitoring
reception of
the PDO.
The number of RxPDOs for each bus node type can be found in the technical data.