Product overview
CX1500-M510, CX1500-B510
149
Version: 1.0
Object
Function code
Resulting COB ID (hex)
Resulting COB ID (dec)
Emergency
0001
0x81 - 0xBF [0xFF]
129 - 191 [255]
TxPDO1
0011
0x181 - 0x1BF [0x1FF]
385 - 447 [511]
RxPDO1
0100
0x201 - 0x23F [0x27F]
513 - 575 [639]
TxPDO2
0101
0x281 - 0x2BF [0x2FF]
641 - 676 [767]
RxPDO2
0110
0x301 - 0x33F [0x37F]
769 - 831 [895]
TxDPO3
0111
0x381 - 0x3BF [0x3FF]
897 - 959 [1023]
RxPDO3
1000
0x401 - 0x43F [0x47F]
1025 - 1087 [1151]
TxPDO4
1001
0x481 - 0x4BF [0x4FF]
1153 - 1215 [1279]
RxPDO4
1010
0x501 - 0x53F [0x57F]
1281- 1343 [1407]
SDO (Tx)
1011
0x581 - 0x5BF [0x5FF]
1409 - 1471 [1535]
SDO (Rx)
1100
0x601 - 0x63F [0x67F]
1537 - 1599 [1663]
Guarding / Heartbeat/
Bootup
1110
0x701 - 0x73F [0x77F]
1793 - 1855 [1919]
The identifiers that result from the DIP switch settings on the coupler are given, as are the identifier regions
for the node addresses 64...127 (not settable in Bus Couplers BK5110, BK5120 and LC5100) in square
brackets. Addresses 1…99 can be set for the Fieldbus Box modules and the BK515x Bus Couplers.
contains a tabular summary of all the identifiers.
Digital inputs
Digital inputs
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x6000
0
Number of
elements
Unsigned8 ro
N
Depending
on type and
fittings
Number of
available
digital 8-bit
input data
blocks
1
1
st
input
block
Unsigned8 ro
Y
0x00
1
st
input
channel
...
...
...
...
...
...
...
0XFE
254
th
input
block
Unsigned8 ro
Y
0x00
254
th
input
channel
Interrupt mask
Interrupt mask