Product overview
CX1500-M510, CX1500-B510
114
Version: 1.0
The 8 bit value is coded as follows:
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
ManSpec.
reserved
reserved
Comm.
reserved
reserved
reserved
Generic
ManSpec. Manufacturer-specific error, specified more precisely in object 1003.
Comm. Communication error (CAN overrun)
Generic An error that is not more precisely specified has occurred (the flag is set at every error message)
Error store
Error store
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1003
0x00
Predefined
error field
(Error
store)
Unsigned8 rw
N
0x00
Object
1003h
contains a
description
of the error
that has
occurred in
the device -
sub-index 0
has the
number of
error states
stored.
1
Actual error Unsigned32 ro
N
None
Last error
state to
have
occurred
...
...
...
--
...
...
...
10
Standard
error field
Unsigned32 ro
N
None
A maximum
of 10 error
states are
stored.
The 32 bit value in the error store is divided into two 16 bit fields:
MSB
LSB
Additional code
Error Code
The additional code contains the error trigger (see
) and thereby a detailed error
description.
New errors are always saved at sub-index 1, all the other sub-indices being appropriately incremented. The
whole error store is cleared by writing a 0 to sub-index 0.
If there has not been an error since power up, then object 0x1003 only consists of sub-index 0 with a 0
entered into it. The error store is cleared by a reset or a power cycle.
As is usual in CANopen, the LSB is transferred first, followed by the MSB.
Sync Identifier
Sync Identifier