Product overview
CX1500-M510, CX1500-B510
24
Version: 1.0
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1006
0
Communica
tion cycle
period
Unsigned32 rw
N
0x0000000
0
Length of
the SYNC
interval in
µs.
If a value other than zero is entered here, the bus node will go into the fault state if, during synchronous PDO
operation, no SYNC telegram is received within the watchdog time. The watchdog time corresponds here to
1.5 times the communication cycle period that has been set - the planned SYNC interval can therefore be
entered.
The I/O update is carried out at the Beckhoff CANopen bus nodes immediately after reception of the SYNC
telegram, provided the following conditions are satisfied:
- Firmware status C0 or above (CANopen Version 4.01 or higher).
- All PDOs that have data are set to synchronous communication (0..240).
- The sync interval has been entered in object 0x1006 and (sync interval x lowest PDO transmission type) is
less than 90ms.
The modules are then synchronised throughout.
Device name
Device name
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1008
0
Manufactur
er Device
Name
Visible
String
ro
N
BK51x0,
LC5100,
IPxxxx-
B510 or
ILxxxx-
B510
Device
name of the
bus node
Since the returned value is longer than 4 bytes, the segmented SDO protocol is used for transmission.
Hardware version
Hardware version
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1009
0
Manufactur
er
hardware-
version
Visible
String
ro
N
-
Hardware
version
number of
the bus
node
Since the returned value is longer than 4 bytes, the segmented SDO protocol is used for transmission.
Software version
Software version