Parameters
Explanation
EC0
Error Code Low-Byte. Not used (always zero)
EC1
Error Code High-Byte. 0x50 = device error, 0x81 = communication
error, 0x00 = error reset
EReg
Error register. 0x81 = device error, 0x91 = communication error
Bit field 0: Comm
Bit field communication error:
0x01
Guarding delayed or failed
0x02
Sync delayed or failed
0x04
Incorrect PDO length
parameterized
0x08
Event timer timeout: RxPDO not
received in time
0x10
Receive queue overrun
0x20
Transmit queue overrun
0x40
CAN bus OFF
0x80
CAN warning limit exceeded
Bit field 1: DevErr
Bit field device error:
0x01
Terminal error
0x02
K-Bus error / IP-Link error
0x03
-
0x04
EEPROM error
0x10
Unsupported terminal plugged in
(BK5110, LC5100)
0x80
Altered HW configuration.