Product overview
CX1500-M510, CX1500-B510
154
Version: 1.0
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x6425
0
Number of
elements
Unsigned8 ro
N
Depending
on type and
fittings
Number of
analog
input
channels
available
1
lower limit
1
st
input
Unsigned16 rw
Y
0x0000
Lower limit
value for 1
st
input
channel
...
...
...
...
...
...
...
0XFE
lower limit
254
th
input
Unsigned16 rw
Y
0x0000
Lower limit
value for
254
th
input
channel
Values different from 0 activate the lower limit value for this channel. A PDO is then transmitted if the value
falls below this limit value. In addition, the event driven mode must be activated (object 0x6423). The data
format corresponds to that of the analog inputs.
Delta function for analog inputs
Delta function for analog inputs
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x6426
0
Number of
elements
Unsigned8 ro
N
Depending
on type and
fittings
Number of
analog
input
channels
available
1
delta value
1
st
input
Unsigned16 rw
Y
0x0000
Delta value
for the 1
st
input
channel
...
...
...
...
...
...
...
0XFE
delta value
254
th
input
Unsigned16 rw
Y
0x0000
Delta value
for the 254
th
input
channel
Values different from 0 activate the delta function for this channel. A PDO is then transmitted if the value has
changed by more than the delta value since the last transmission. In addition, the event driven mode must
be activated (object 0x6423). The data format corresponds to that of the analog inputs (delta value: can only
have positive values).
2.3.9.3
Objects and Data of the BX5100/BC5150
Access to located flags
Access to located flags