![Beckhoff CX1500-B310 Скачать руководство пользователя страница 155](http://html1.mh-extra.com/html/beckhoff/cx1500-b310/cx1500-b310_manual_2719532155.webp)
Product overview
CX1500-M510, CX1500-B510
155
Version: 1.0
Index
sub index
Name
Type
Attrb.
Map.
Default
Value
Meaning
0x2F00
0
Number of
sub index
Unsigned8 ro
N
128
Number of
sub index
1
Flag
Unsigned32 rw
N
none
Flag
%MB0..3
2
Flag
Unsigned32 rw
N
none
Flag
%MB4..7
...
...
...
...
...
...
...
128
Flag
Unsigned32 rw
N
none
Flag
%MB508..5
11
Index
sub index
Name
Type
Attrb.
Map.
Default
Value
Meaning
0x2F01-
0x2F07
0
Number of
sub index
Unsigned8 ro
N
128
Number of
sub index
1
Flag
Unsigned32 rw
N
none
Flag
%MBx..x+4
2
Flag
Unsigned32 rw
N
none
Flag
%MBy..y+4
...
...
...
...
...
...
...
128
Flag
Unsigned32 rw
N
none
Flag
%MBz...z
+14
AMS NetId
NetId
Index
sub index
Name
Type
Attrb.
Map.
Default
Value
Meaning
0x5FFE
0
NetId
String
rw
N
1.1.1.1.1.1
AMS Net Id
2.3.10
ADS-Communication
2.3.10.1
ADS Services
Local process image task 1 port 800 or port 801
Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is
important to ensure that they are not used by the local PLC, because the local controller will overwrite these
values. The data is not associated with a watchdog, and therefore must not be used for outputs that would
have to be switched off in the event of a fault.
Index group
Meaning
Index offset (value range)
0xF020
Inputs
0...2047
0xF030
Outputs
0...2047
0x4020
Flags
0...4095