Product overview
CX1500-M510, CX1500-B510
118
Version: 1.0
• All guarding parameters
• Limit values, delta values and interrupt enables for analog inputs
Parameters directly stored in the terminals by way of register communication are immediately stored there in
non-volatile form.
Load default values
Load default values
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1011
0
Restore
Parameter
Unsigned8 ro
N
4
Number of
reset
options
1
Restore all
parameters
Unsigned32 rw
N
1
Resets all
parameters
to their
default
values
4
Set
manufactur
er Defaults
Unsigned32 rw
N
1
Resets all
coupler
parameters
to
manufactur
er’s settings
(including
registers)
Writing the string
load
in ASCII code (hexadecimal 0x64616F6C) into sub-index 1 resets all parameters to
default values (as initially supplied)
at the next boot (reset)
.
(The byte sequence on the bus including the SDO protocol: 0x23 0x11 0x10 0x01 0x6C 0x6F 0x61 0x64).
This makes the default identifiers for the PDOs active again.
Emergency identifier
Emergency identifier
Index
Sub-index Name
Type
Attribute
Mapping
Default
value
Meaning
0x1014
0
COB-ID
Emergency
Unsigned32 rw
N
0x0000008
0, +
NodeID
Identifier of
the
emergency
telegram
The bottom 11 bits of the 32 bit value contain the identifier (0x80=128 dec). The MSBit can be used to set
whether the device sends (1) the emergency telegram or not (0).
Alternatively, the bus node's diagnostic function can also be switched off using the
Device diagnostics
bit in
the K-Bus configuration (see object 0x4500).