PROGRAMMING
INSTRUCTIONS
SINUS PENTA
405/452
50.3.2.
F
ROM THE
S
INUS
P
E NTA T O THE
M
A S TE R
Word
1) Code
2) Description
3) Range
4) Unit of
Measure
5) Scaling
1
Alarms
–
–
–
2
M026
Output Current
0
65000
A
x 10
3
M004
Motor Speed
– 32000
+ 32000
rpm
x 1
4
Third measure that may
be configured with
P330
All the measures
See selected
measure
See selected
measure
5
Fourth measure that may
be configured with
P331
All the measures
See selected
measure
See selected
measure
6
DIN
Digital Inputs
–
–
–
7
DOU
Digital Outputs
–
–
–
8
REF
REF Analog Input
– 16380
+ 16380
–
–
9
AIN1
AIN1Analog Input
– 16380
+ 16380
–
–
10
AIN2
AIN2 Analog Input
– 16380
+ 16380
–
–
Word 1: Alarms
The
Status
and
Alarms
are displayed over the fieldbus in the following format:
bit [15..8]
bit [7..0]
Status
Alarms
The
Status
codes may be found in
Table 125
.
The
Alarm
codes may be found in Table 122
.
Word 2: Output Current
The output current measure (
M026
) is displayed as a value that must be divided by 10 to obtain the actual
motor current.
As a result, if the returned value from the Sinus Penta to the Master is 100, then the actual output motor current is 10A.
bit [15..8]
bit [7..0]
Output Current
Word 3: Motor Speed
The output motor speed (
M004
) is displayed as follows:
bit [15..8]
bit [7..0]
Motor Speed
Words 4 & 5: Third & Fourth measure that may be configured with P330 & P331
Words 4 & 5 may be configured with
P330
and
P331
– more details are given in the FIELDBUS PARAMETERS MENU.
Both words 4 & 5 are represented as follows:
bit [15..8]
bit [7..0]
Mxxx
represented by
P330
and
P331
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...