PROGRAMMING
INSTRUCTIONS
SINUS PENTA
217/452
Testing Variable A for MPL1 (2, 3, 4): P353, (P362, P371, P380)
If an analog variable is selected, a logic TEST is performed to obtain a TRUE/FALSE Boolean signal.
Eight different tests are available, that can be performed for selected variable A and its comparing value A:
Table 55: Test functions.
GREATER THAN
Selected variable > comparing value
GREATER THAN/EQUAL TO
Selected variable
comparing value
LOWER
Selected variable < comparing value
LOWER THAN/EQUAL TO
Selected variable
comparing value
ABS, GREATER THAN
Absolute value (selected variable) > comparing value
ABS, GREATER THAN/EQUAL TO Absolute value (selected variable)
comparing value
ABS, LOWER
Absolute value (selected variable) < comparing value
ABS, LOWER THAN/EQUAL TO
Absolute value (selected variable)
comparing value
NOTE
This parameter can be accessed only if the operating mode of the selected digital output
is > 2. Example: MPL1
P350
>2.
Operation on variable B, digital output MPL1 (2, 3, 4): P354,
(
P363
,
P372
,
P381
)
If an analog variable is selected, a logic TEST is performed to obtain a TRUE/FALSE Boolean signal.
Eight different tests are available, that can be performed for selected variable B and its comparing value B (see Table
57).
NOTE
This parameter can be accessed only if the operating mode of the selected digital output
is > 2 and < 9. Example: MPL1 2<
P350
<9.
Reference threshold for P351 ( P360, P369, P378) in MPL1: P355,
(
P364
,
P373
,
P382
)
Defines the comparing value of Test A with the first selected variable.
NOTE
This parameter can be accessed only if the operating mode of the selected digital output
is > 2. Example: MPL1
P350
>2.
Reference threshold for P352 ( P361, P370, P379) in MPLx: P356,
(
P365
,
P374
,
P383
)
Defines the comparing value of Test B with the first selected variable.
NOTE
This parameter can be accessed only if the operating mode of the selected digital output
is > 2. Example: MPL1
P350
>2.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...