SINUS PENTA
PROGRAMMING
INSTRUCTIONS
170/452
P249 PID Reference Ramp Up Time
P249
Range
0
32700
Function of
P251
Default
0
0 s
Level
ENGINEERING
Address
849
Function
This parameter defines the ramp up time of the PID regulator reference from 0%
to the max. allowable absolute value (max. {|
P245
|,|
P246
|}).
P250 PID Reference Ramp Down Time
P250
Range
0
32700
Function of
P251
Default
0
0 s
Level
ENGINEERING
Address
850
Function
This parameter defines the ramp down time of the PID regulator reference, from
max. allowable value (max. {|
P245
|,|
P246
|}) to 0%.
P251 Unit of measure of PID Ramp
P251
Range
0
3
0: 0.01 s
1: 0.1 s
2: 1.0 s
3: 10.0 s
Default
1
1: 0.10 s
Level
ENGINEERING
Address
851
Function
This parameter defines the unit of measure for the PID reference ramp times.
It defines the unit of measure for the time of the third ramp of the PID reference
P249
and
P250
, so that the allowable range becomes 0s – 327000s.
Example:
P251
Range P249 – P250
Value
Coding
Min.
Max.
0
0.01 s
0
327.00 s
1
0.1s
0
3270.0 s
2
1.0 s
0
32700 s
3
10.0 s
0
327000 s
NOTE
Factory-setting: the PID reference ramp is zero; if a given ramp time is set up, the ramp will
be rounded off (50% at the beginning and at the end of the ramp). See parameters
P252
and
P253
.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...