PROGRAMMING
INSTRUCTIONS
SINUS PENTA
317/452
C160 DCB Input
C160
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1160
Control
IFD and VTC
Function
For other types of control, this function has no effect even if
C160
0.
The DCB command enables
DC braking
for a time period depending on the speed
value determining the input activation.
See the DC BRAKING MENU for more details.
C161, C162 UP and DOWN Inputs
C161 C162
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1161, 1162
Function
This function increases (
UP
) or decreases (
DOWN
) the reference for which the
UpDown source from MDI has been
selected
by adding a quantity
to the reference
itself.
This also depends upon the following parameters:
C163
Up/Down Reset
P067
Up/Down Ramp Time
P068
Store Up/Down value at power off
P068a
Speed/Torque Up/Down Reset at stop
P068b
PID Up/Down Reset at stop
P068c
Speed/Torque Up/Down Reset at sources changeover
P068d
PID Up/Down Reset at sources changeover
P069
Up/Down Reference range
C163 Reset Up/Down Input for Speed/Torque Reference
C163
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1163
Function
This function sets to zero the reference
variation
obtained via the
UP
or
DOWN
inputs
or the
▲
and
▼
keys located on the display/keypad. The Up/Down reference
(Speed/Torque only) may also be reset using different functions (see
P068a – P068c
).
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...