PROGRAMMING
INSTRUCTIONS
SINUS PENTA
129/452
P128 (P138, P148) Proportional Coefficient for Minimum Error
P128 (Motor n.1)
P138 (Motor n.2)
P148 (Motor n.3)
Range
0
65000
0.00
650.00
Default
1000
10.00
Level
BASIC
Address
728,738,748
Control
VTC and FOC
Function
This parameter sets the min. proportional coefficient for the speed regulator.
Default value (10): if a speed error of 1% occurs, the regulator will require 10% of
the motor rated torque.
P129 (P139, P149) Proportional Coefficient for Maximum Error
P129 (Motor n.1)
P139 (Motor n.2)
P149 (Motor n.3)
Range
0
65000
0.00
650.00
Default
1000
10.00
Level
BASIC
Address
729,739,749
Control
VTC and FOC
Function
This parameter sets the max. proportional coefficient for the speed regulator.
Default value (10): if a speed error of 1% occurs, the regulator will require 10% of
the motor rated torque. This parameter may be accessed only if the min. and max.
error thresholds are different (P130
P131 for Motor1, P140
P141 for Motor2,
P150
P151 for Motor3).
P130 (P140, P150) Min. Error Threshold
P130 (Motor n.1)
P140 (Motor n.2)
P150 (Motor n.3)
Range
0
32000
0.00
320.00
Default
100
1.00%
Level
BASIC
Address
730,740,750
Control
VTC and FOC
Function
This parameter determines the min. error threshold.
In case of speed errors lower than or equal to the min. threshold, parameters P126
and P128 will be used.
P131 (P141, P151) Max. Error Threshold
P131 (Motor n.1)
P141 (Motor n.2)
P151 (Motor n.3)
Range
0
32000
0.00
320.00
Default
100
1.00%
Level
BASIC
Address
731,741,751
Control
VTC and FOC
Function
This parameter sets the max. error threshold.
If P130 = P131 or in case of speed errors greater than or equal to the max.
threshold, parameters P125 and P129 will be used.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...