C143 (C144, C145, C146) Reference 1 (2, 3, 4) Selection
C143 (C144, C145,
C146)
Range
0
9
0 ÷ 11 if ES847 is in
0: Disabled
1: REF
2: AIN1
3: AIN2
4: Frequency input
5: Serial Link
6: Fieldbus
7: Keypad
8: Encoder
9: UpDown from MDI
10: XAIN4
11: XAIN5
Default
C143
= 1,
C144
= 2
C145
÷
C146
= 0
C143
= 1: REF,
C144
= 2: AIN1
C145
÷
C146
= 0 : Disabled
Level
C143
÷
C144
ADVANCED;
C145
÷
C146
ENGINEERING
Address
1143 (1144, 1145, 1146)
Function
This parameter selects the sources for the speed (or torque) reference.
The reference resulting from the sum of the selected sources represents the drive
speed or torque reference. If the PID action has been set as reference
C294 =
Reference
, the drive speed or torque references shall only be given by the PID
output and not by the sources set in
C143 ÷ C146
.
Reference sources 10 and 11 can be selected only after setting XAIN in parameter
R023.
C147 Torque Limit Input
C147
Range
0
9
0: Disabled
1: REF
2: AIN1
3: AIN2
4: Frequency input
5: Serial Link
6: Fieldbus
7: Keypad
8: Encoder
9: UpDown from MDI
10: XAIN4
11: XAIN5
Default
0
0: Disabled
Level
ENGINEERING
Address
1147
Control
VTC and FOC
Function
If a speed control with FOC or VTC control algorithms is used, an external torque
limit can be used. Parameter
C147
selects the Torque Limit source. The torque
ramp times set in
P026–P027
will be applied to the torque limit reference source
that has been selected. The external torque limit may be disabled by closing the
digital input set with
C187.
Limiting sources 10 and 11 can be selected only after setting XAIN in parameter
R023
.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...