SINUS PENTA
PROGRAMMING
INSTRUCTIONS
26/452
4.
PROGRAMMABLE
FUNCTIONS
4 .1 .
Multimotor
The Sinus Penta drive provides 3 separate sets of parameters allowing configuring three control algorithms for 3 types
of motors:
C009
Number of configured motors =2
C173
Digital input for Motor 2 = MDI6
When MDI6 is open, the parameters relating to Motor 1 are used for the motor control; when MDI6 is closed, the
parameters relating to Motor 2 are used for the motor control (see the MOTOR CONTROL MENU and the
MULTISPEED MENU).
4 .2 .
Voltage/Frequency Pattern
When using a Volt/Freq IFD control algorithm (e.g.
C010 = V/F IFD
for Motor 1), you can select different types of V/f
patterns (see the V/f Pattern (IFD Only) section).
4 .3 .
Slip Compensation
When using a Volt/Freq IFD control algorithm (e.g.
C010 = V/F IFD
for Motor 1), you can set the slip compensation
function for a more accurate speed control (see the Slip Compensation (IFD Only) section).
4 .4 .
Speed Searching
When using a Volt/Freq IFD control algorithm (e.g.
C010 = V/F IFD
for Motor 1), you can set the speed searching
function for the motor speed of rotation, which is useful when the drive controls a motor which is already running (as
for motors connected to fans). See the SPEED SEARCHING MENU for more details.
4 .5 .
Controlled Stop in Case of Power Failure (Power Down )
See the POWER DOWN MENU to set a controlled stop in case of power failure.
4 .6 .
DC Braking
When using a Volt/Freq IFD or Vector Torque VTC control algorithm, you can set DC braking at start or at stop. The
DCB Hold function can be set for the Volt/Freq IFD function. See the DC BRAKING MENU for more details.
4 .7 .
Motor Thermal Protection
The Motor Thermal Protection function protects the motor against possible overloads. This function can be obtained via
a PTC acquired in AIN2 analog input—up to 6 PTCs can be series-connected—or it can be a software protection
implemented through an algorithm reproducing the motor thermal image.
See the MOTOR THERMAL PROTECTION MENU for more details.
For more details about using AIN2 input, please refer to the Sinus Penta’s
Installation Instructions Manual.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...