SINUS PENTA
PROGRAMMING
INSTRUCTIONS
314/452
The figure below illustrates the processing logic diagram for the
START
,
REV, Cw/CCw
functions and the
START,
STOP, REV
keys
on the display/keypad, if the
STOP
function is programmed.
Figure 49: Controlling Run and Direction when the STOP Input is programmed.
C152 ENABLE–S Input
C152
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1152
Function
This is a safety ENABLE: if this function is enabled, the drive activates only if both
ENABLE
and
ENABLE–S
inputs are active.
NOTE
The
ENABLE–S
signal cannot be delayed by software timers: if a timer is programmed
for the terminal relating to
ENABLE–S
, it will have no effect on the
ENABLE–S
function, whereas it will normally delay other functions programmed for the same
terminal.