PROGRAMMING
INSTRUCTIONS
SINUS PENTA
365/452
4 2.3.
Thermal Protection Trip Delay
The graph below shows the thermal protection trip delay depending on the IEC Class and the current flowing (which is
supposed to be constant).
Parameter
C266
(trip current) is factory set to 105%.
Figure 62: Trip delay of alarm A075 based on the IEC Class.
Example: The protection level is compliant with IEC Class 30. If the current flowing is 200% of the FLC, alarm
A075
will trip after approx. 480s (8 minutes).