PROGRAMMING
INSTRUCTIONS
SINUS PENTA
251/452
3 1.2.
List of Parameters C001 to C004
Table 64: List of parameters C001 to C004.
Parameter
FUNCTION
User Level
MODBUS Address
Default Values
C001
Minimum carrier frequency
ENGINEERING
1001
See Table 73 and Table 77
C002
Maximum carrier frequency
ENGINEERING
1002
See Table 73 and Table 77
C003
Number of pulses
ENGINEERING
1003
1:[24]
C004
Silent modulation
ENGINEERING
1004
See Table 73 and Table 77
The default value and the max. value of carrier frequency (
C001
and
C002
) depend on the drive size.
To check those values, see Table 73 and Table 77.
C001 Minimum Carrier Frequency
C001
Range
1600 ÷ 16000
Depending on the drive model
1600 ÷ 16000 Hz
Depending on the drive model
– see Table 73
and Table 77.
Default
See Table 73 and Table 77
Level
ENGINEERING
Address
1001
Control
IFD and VTC
Function
It represents the min. value of the modulation frequency being used.
NOTE
The min. value set in
C001
cannot exceed the max. value set in
C002
. Increase the max.
value in
C002
if you need to increase the min. value and if
C001
equals
C002
.
C002 Maximum Carrier Frequency
C002
Range
1600 ÷ 16000
Depending on the drive size
1600 ÷ 16000 Hz
Depending on the drive model
– see Table 73
and Table 77
Default
See Table 73 and Table 77
Level
ENGINEERING
Address
1002
Function
It represents the max. value of the modulation frequency being used.
As per FOC control, the modulation frequency set in
C002
is used only if
exceeding 8 kHz (when the max. allowable carrier frequency is > 8kHz).
Otherwise, the max. carrier frequency allowed is used for the models
implementing a carrier frequency <8 kHz, independently of
C002
.
NOTE
The max. value set in
C002
cannot be lower than the min. value set in
C001
. Decrease
the min. value in
C001
if you need to decrease the max. value and if
C001
equals
C002
.
NOTE
The max. value in
C002
also determines the max. allowable speed value for the
selected motor, in order to ensure a minimum number of pulses per period of frequency
produced. This value is 16 for maximum carrier frequency (max.
C002
value) greater
than 5kHz and 10 for lower maximum carrier frequency (see Table 73 and Table 77).
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...