PROGRAMMING
INSTRUCTIONS
SINUS PENTA
293/452
34.1.1.
C
O MMA ND
S
O URCE S
The drive commands
may be sent from the following sources:
0: Disabled
1: Terminal board A
2: Serial link (with MODBUS protocol)
3: Fieldbus (fieldbus on option board)
4: Terminal board B
5: Keypad (remotable display/keypad)
The factory-setting enables only Terminal Board A (
C140
=1 and
C141
=1) as a command source (see also the DIGITAL
INPUTS MENU). Both Terminal board A and B refer to the same terminal board located on the control board, but allow
switching between one set of START, STOP, REVERSE commands sent to three terminals to a different set of
commands sent to three different terminals.
Most commands may be delayed (when enabled or disabled): refer to the TIMERS MENU.
Figure 45: Selecting the command sources.
If the keypad is not selected as a command source or if the
STOP
input function is enabled (
C150
0), more than one
command source may be enabled at a time. In this case, the logic function implemented by the drive for the terminals
of all active command sources is the following:
AND
for the terminals allocated to the
ENABLE, ENABLE–S, External Alarms n.1, n.2, n.3
functions;
OR
for all other terminals
.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...