PROGRAMMING
INSTRUCTIONS
SINUS PENTA
267/452
C020 (C063,C106) Motor No-Load Power
C020 (Motor 1)
C063 (Motor 2)
C106 (Motor 3)
Range
0
1000
0.0
100.0%
Default
0
0.0%
Level
ADVANCED
Address
1020 , 1063, 1106
Function
This parameter defines the power absorbed by the motor at rated voltage and rated
rpm when no load is connected to the motor.
C021 (C064,C107) Motor No-Load Current
C021 (Motor 1)
C064 (Motor 2)
C107 (Motor 3)
Range
1
100
1
100%
Default
0
0%
Level
BASIC
Address
1021, 1064, 1107
Function
This parameter defines the current absorbed by the motor at rated voltage and
rated rpm when no load is connected to the motor. It is expressed as a percentage
of the motor rated current
C018
(
C061
,
C104
). For a proper tuning of the current
loops required for FOC control, enter a value other than zero.
If the stator resistance is tuned (
I073
= [1: Motor Tune]);
1074
= (0: All no
rotation)) and the no load current parameter is zero, a value for a first attempt is
assigned to this parameter, depending on power and pole pairs of the connected
motor.
C022 (C065,C108) Motor Stator Resistance
C022 (Motor 1)
C065 (Motor 2)
C108 (Motor 3)
Range
0
32000
0.000
32.000
Default
See Table 76 and Table 80
Level
ADVANCED
Address
1022, 1065, 1108
Function
This parameter defines stator resistance Rs.
If a star connection is used, it matches with the value of the resistance of one
phase (half the resistance measured between two terminals); if a delta connection
is used, it matches with 1/3 of the resistance of one phase.
Autotune is always recommended.
C023 (C066,C109) Motor Leakage Inductance
C023 (Motor 1)
C066 (Motor 2)
C109 (Motor 3)
Range
0
32000
0.00
320.00mH
Default
See Table 76 and Table 80
Level
ADVANCED
Address
1023, 1066, 1109
Function
This parameter defines the global leakage inductance of the connected motor.
If a star connection is used, it matches with the value of the inductance of one
phase; if a delta connection is used, it matches with 1/3 of the inductance of one
phase.
Autotune is always recommended.
NOTE
With the Autotuning function, calculate the value of the leakage inductance (
C023
). From the
resulting value, manually subtract the value in mH of the output inductance (if any).
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...