SINUS PENTA
PROGRAMMING
INSTRUCTIONS
194/452
P273 MDO1: Testing Variable A
P273
Range
0
7
0: >
1:
2: <
3:
4: ABS(x) >
5: ABS(x)
6: ABS(x) <
7: ABS(x)
Default
0
0: >
Level
ADVANCED
Address
873
Function
This parameter defines the test to be performed for the variable detected by
P271
using
P275
as a comparing value.
P274 MDO1: Testing Variable B
P274
Range
0
7
0: >
1:
2: <
3:
4: ABS(x) >
5: ABS(x)
6: ABS(x) <
7: ABS(x)
Default
3
3:
Level
ADVANCED
Address
874
Function
This parameter defines the test to be performed for the variable detected by
P272
using
P276
as a comparing value.
P275 MDO1: Comparing Value for Test A
P275
Range
–32000
32000
–320.00 %
320.00 %
% of the full-scale value of selected variable A
, see Table 41.
Default
50
50 rpm
Level
ADVANCED
Address
875
Function
This parameter defines the comparing value with the selected variable for test A.
P276 MDO1: Comparing Value for Test B
P276
Range
–32000
32000
–320.00 %
320.00 %
% of the full-scale value of selected variable B
, see Table 41.
Default
10
10 rpm
Level
ADVANCED
Address
876
Function
This parameter defines the comparing value with the selected variable for test B.
Содержание SINUS PENTA
Страница 142: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 142 452 Figure 21 Curve voltage speed implemented by AO1 Example 5 ...
Страница 184: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 184 452 Figure 33 ANALOG Mode Figure 34 DOUBLE DIGITAL Mode ...
Страница 185: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 185 452 Figure 35 General structure of the parameterization of a digital output ...
Страница 348: ...SINUS PENTA PROGRAMMING INSTRUCTIONS 348 452 Figure 57 Power Down Example ...
Страница 435: ...PROGRAMMING INSTRUCTIONS SINUS PENTA 435 452 ...