Electrical data basic units
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
Baumüller Nürnberg GmbH
72
3.4
3.4.1.4 Electrical data BM554X universal units
m
Without charging resistor BM554X-X
T
/BM554X-X
G
/BM554X-X
I
BM5
5
4
3
BM5
5
4
4
BM5
5
4
5
BM5
5
4
6
12)
Rated input power
1)2)
48 kVA
58 kVA
73 kVA
94 kVA
Rated input current
1)2)
(I
eff
)
70.0 A
84 A
105 A
136 A
Total harmonic distortion input current
1)2)
(THD
I
)
60 %
59 %
45 %
38 %
Max. input current
2)
(I
eff
)
105 A
105 A
133 A
187 A
Rated DC link voltage
1)
540 V
DC
DC link capacitance (internal)
1880
F
2350
F
3055
F
3760
F
DC link capacitance (external), permitted
Refer to
DC link discharging time (int. DC link capacitance)
45 s
55 s
70 s
90 s
Waiting period between two
switching-on operations
None
Output voltage
1)3)
(U
AC
)
3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
14)
0 Hz to 450 Hz
Rated output current
1)5)6)7)15)
(I
AC
)
at 4 kHz
4)
80 A
100 A
130 A
150 A
Rated output current
1)5)6)7)15)
(I
AC
)
at 8 kHz
4)
75 A
72 A
94 A
105 A
Output peak current
1)5)6)8)15)
(I
AC
)
at 4 kHz
4)
120 A
130 A
170 A
200 A
Output peak current
1)5)6)8)15)
(I
AC
)
at 8 kHz
4)
90 A
94 A
130 A
150 A
Max. peak current period
8)9)
60 s
Power supply DC link terminals
11)
Max. 90 kW
Brake resistor current, permitted (Î)
Max. 67 A
Max. 100 A
Brake resistor external
v
12
v
7.4
16)
Brake resistor threshold (Û)
780 V
Brake resistor peak power
53 kW
80 kW
Permitted continuous brake resistor power external
36 kW
45 kW
58 kW
75 kW
Power loss referring to the power input
1080 W
1350 W
1740 W
2000 W
Power loss referring to control voltage
112 W
Power loss of fan of device referring to 230 V
AC
10)
87 W
Current of integrated brake control
Max. 8.0 A
13)
Cooling air requirement power heatsinks
260 m
3
/h
210 m
3
/h
Cooling air requirement internal space
60 m
3
/h
Requirements to the water cooling
Refer to