![Baumuller b maXX 5500 Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/baumuller/b-maxx-5500/b-maxx-5500_instruction-handbook-manual_2711410051.webp)
Technical Data
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
51
3
1)
Voltage dips of the power supply voltage phase-to-phase down to 0 V are prohibited, no matter how short
The error „power supply not ready-to-operate“ is generated if the supply voltage falls below U
ACmin
for t > 0.1 s.
2)
Rated voltage is 400 V.
With lower supply voltages the output power of the device is reduced. Refer to correction factors, in case the operating conditions were
changed
3)
The control voltage must accord to PELV (EN 61800-5-1, chapter 3.21) or SELV (EN 61800-5-1, chap. 3.35).
At control voltage of < 24 V the ventilation power output is reduced. Therefore, it may be necessary, to reduce the output currents as
well.
4)
Required for UL 508C, only.
5)
Rate of change of the power supply frequency 1 Hz/s at a maximum (EN 61000-2-4, class 3).
6)
The connection and operation of a device with the identification BM5XXX-X
T
XX at an IT system or a grounded delta system, is
not
permitted.
7)
Valid for BM554X/BM555X/BM556X, BM564X/BM565X/BM566X cooling versions S and A and BM557X cooling version A.
8)
The distortion factor of the input current of following devices
BM55XX-XR
/XS
/XW
,
BM56XX-XR
/XS
/XW
and
BM57XX-XR
/XS
/XW
is approx.
twice as much
the factor at operation with power choke.
The user has to check with the local power supplier whether an operation without power choke is allowed.
9)
The error No. 93 is displayed and a damage of the device is possible if the power supply voltage is higher than the permitted power
supply voltage
10)
The power supply voltage phase-to-phase must increase or decrease linearly within 800 µs between zero crossing and 150 V.
Commutating dips
EN 61800-3, chapter 5.2.1, class 3
Depth of dip < 40 %, area < 250 % x
degrees
Voltage dips
EN 61800-3:2004 and A1:2012
10 % to 80 %
1)
Voltage variations/-fluctuations
EN 61200-2-4, class 3
+/-10 %
10)
+10 % to -15 % at a period of
b
1 min
Short-circuit Current Rating (SCCR)
4)
65 kA
Rated supply voltage /
-frequency (U
AC
) fan
7)
BM554X-S/A, BM555X-S/A, BM556X-S/A,
BM564X-S/A, BM565X-S/A,
BM566X-S/A
230 V
10 %
50/60 Hz
BM557X-A
3 x 400 V
10 %
50/60 Hz
Control voltage
3)
(U
DC
)
EN 61131-2:1994, table 7
+ 24 V -15 % / +20 %
NOTE!