![Baumuller b maXX 5500 Скачать руководство пользователя страница 203](http://html.mh-extra.com/html/baumuller/b-maxx-5500/b-maxx-5500_instruction-handbook-manual_2711410203.webp)
Voltage input
Current input
Resolution
14 bit
Type
Differential input
Input resistance
ca. 50 k
ca. 100
Input current
Max. 250 µA
Min. (0)
4 A, max.
20 mA
Input voltage
-10 V to +10 V
Max. 2 V
Sampling rate
125 µs
Power supply encoder
Max. 250 mA per connection
Installation
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
203
7
Analog inputs
Linearity error inputs in LSB
Error
Min
Type
Max
DNL
0
2
4
INL
0
3
6
Offset
0
3
6
Gain
0
3
6
NOTE!
The connections of the cables of the analog channels must be done shielded.
Blade terminals with 6.3 mm width are available for connecting the shields.